Products

 

        SHIPPING SPECIFICATIONS

MODEL LENGTH
"A" (mm)
WIDTH
"B" (mm)
HEIGHT
"C" (mm)
WEIGHT
"D" (kg)
PM 15.5 1400.0 385 1280 600
PM 34.5 1625.6 885 1280 755
PM 52 2000 885 1280 937
PM 75 2000 885 1280 1028
PM 97 2000 885 1400 1067
PM 132 2500 1100 1400 1365
PM 165 2500 1100 1400 1670
PM 250 2700 1200 1650 2290
PM 313 3000 1200 1715 3215
PM 375 3000 1200 1810 3447
PM 500 3000 1400 2200 3800
PM 775 3500 1400 2200 5380
PM 880 3600 1400 2200 5820

Click here to view Cummins Specifications

 

Genset Model Perkins
engine model
Prime Rating at 1800 RPM Typical
Power Factor
Standby Rating at 1800 RPM HZ
KW kVA KW kVA
PM15.5 103-10 11.2 14.0 0.8 27.4 15.5 60
PM34 3.1524 24.8 31.0 0.8 27.8 34.0 60
PM52 4.236 37.7 47.1 0.8 41.6 52.0 60
PM75 T4.236 54.4 68.0 0.8 60.0 75.0 60
PM97 1004TG 70.4 88.0 0.8 77.6 97.0 60
PM132 1006TG2A 97.5 122.0 0.8 105.6 132.0 60
PM165 1006TAG 121.0 151.0 0.8 132.0 165.0 60
PM250 1306E87TA 185.0 231.0 0.8 200.0 250.0 60
PM313 2006TG2A 228.0 285.0 0.8 250.4 313.0 60
PM375 2006TWG2 273.0 341.0 0.8 300.0 375.0 60
PM500 3008TAG2A 367.0 459.0 0.8 400.0 500.0 60
PM775 3012TAG1A 564.0 705.0 0.8 620.0 775.0 60
PM880 3012TAG3A 640 800.0 0.8 740.0 880.0 60
INDUSTRIAL GENERATOR SETS -15.5 to 880 kVA
Engine

Perkins water-cooled, direct injection, four-stroke diesel engine. Perkins means diesel and gas power in more than 160 countries, trusted as primemover by more than 600 original equipment manufacturers worldwide. Perkins dominates the world market in genset primemovers from 15.5  to 880 kVA. Over 300,000 engines produced each year in 13 countries and over 14 million units produced since 1930. Truly a global leader in diesel primemovers.

Baseframe

The engine/alternator assembly and radiator are mounted on anti-vibration mounts on a substantial steel fabricated and welded base frame constructed to include a base fuel tank with a minimum capacity for continuous operation of 8 hours. Fuel tank fittings include fuel-fill points, fuel level indicator, breather, drain plug, and flexible fuel feed and return lines.

AC/DC Control Panel

Constructed from heavy gauge sheet metal, it has instrumentation mounted on a hinged front door, giving access to internal control circuitry. Standard instruments are:

  • Ammeter with selector switch
  • Charging Ammeter
  • Voltometer and phase selector switch
  • Suitably scaled frequency meter
  • Coolant temperature gauge
  • Lube-oil pressure gauge
  • Keystart engine protection module
  • Moulded case circuit breaker
  • Automatic engine shutdown for low oil pressure
  • Atuomatic engine shutdown for high water temperature

The panel comes complete with all internal wiring, control circuit relays, protective fuses, terminations etc., and all circuit compenents/ control switches.

Standard Accessories

  • 12/24V axial type starter motor
  • High capacity charging alternator
  • Tropicalized radiator
  • Fan guard
  • Mechanical fuel lift pump
  • Heavy duty air cleaner
  • Governing to BS. 5514/A1, DIN 6271, and ISO 3046/1
  • Anti-vibration mountings
  • Subframe and 8 hours continuous running base fuel tank with fuel level gauge
  • Automatic shutdown protection for high coolant temperature and low Lub oil pressure with indicating lights
  • Set-mounted AC control panel provided with standard instrumentation
  • Suitably rated-moulded case circuit breaker in heavy gauge, powder-coated mobile enclosure
Alternator

Mecc-Alte. The result of extensive studies and researches aiming to be at the forefront of technological development in an era where superior technology is the winnning card. Manufactured according to the demanding standards of the European Community CE, Canadian CSA, and the prestigeous CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS 4999-5000. Manufactured from probably the most modern-fully automated ISO 9001 -certified alternator factory in the world.

But Mecc-Alte's greatest pride is its revolutionary UVR6 voltage regulator-the heart and soul of any alternator. To date, still is unmatched by any other alternator maker in the world. With its 40,000 operating hours median time between breakdowns, Perkins is probably the only generator set in the world carrying a 3-year warranty* for its Mecc-ALTE UVR6 voltage regulators-the true measure of confidence.

(* incidental expenses for its replacement, eg. transportaion, lodging, etc. are excluded)

Regulation

The self-regulation is obtained through an electronic regulator. The regulator is fed by an auxiliary winding which guarantees an almost constant supply under any possible operating condition of the generator.

Voltage Regulation

The voltage can be regulated by the "VOLT" potentiometer of the electronic regulator. By connecting a 100KiloOhm potentiometer in the proper terminals; it is also possible to obtain a remote voltage regulation in a range of 55% of the related voltage.

Transient Voltage and Response Times

At full load and no load, at constant speed, there is a transient voltage variation lower than 15% of the rated voltage. In such conditions, the 3% voltage resetting will occur in 0.2 seconds for powers up to 300 kVA, while for higher powers it will occur in 0.3 seconds. Make reference to the user's manual for more details.

Overload

The permissible overloads are of 300% for 20 seconds, of 50% for 2 minutes and of 10% for 1 hour every 6 hours of operation.

Parallel operation

Can function in parallel among themselves, notwithstanding the type of alternator, and/or in parallel with the mains provided that they are equipped with the special device. This device is available upon request for the alternators up to 375 kVA, while the alternators with a higher power are equipped with this as standard equipment. In case of parallel wiht the mains we offer the P.F.R. 96/1 electronic device which controls the alternator's reactive current and/or power factor of the alternator.

Radio Interference Suppression

The standard generators comply with the specification VDE 0875, degree "G" and "N" and with the basic safety requirements of the European regulation on electromagnetic compatibility; by applying the European standards EN 50081-1 and EN 50082-1, we comply with the above mentioned regulation.

On request we can supply filters for more restrictive specifications such as VDE 0875, degree "K", MIL 461-462 D, etc.

E-mail us for questions or inquiries
Or call the main office at (63-2) 532-29-51